Industrial Ventilation Hood CFM Calculator
Determine exhaust hood volumetric airflow (CFM), capture velocity, hood static entry loss, and transport duct sizing per ACGIH Industrial Ventilation standards.
Hood Configuration & Contaminant
Duct Transport Standards
Ventilation Exhaust Sizing
Recommended Tools & Equipment
Tested hardware and components for high reliability
Frequently Asked Questions
Why does adding a flange to an exhaust hood reduce required airflow by 25%?
A plain duct opening draws air equally from all directions (a full 360° sphere), wasting fan CFM pulling clean air from behind the hood face. A flange blocks airflow from the rear, focusing suction entirely forward into a 180° hemisphere and slashing required fan power by 25%.
Why does capture velocity decrease with the square of distance (1/X²)?
In exhaust ventilation, suction velocity drops precipitously away from the opening because air expands radially across a widening hemisphere. At just one duct diameter away, capture velocity drops to only 10% of hood face velocity.
What is minimum transport velocity in industrial ductwork?
Minimum transport velocity is the continuous airspeed required inside ductwork to keep solid particulate suspended in the air stream. If velocity drops below threshold (e.g. 3,500 FPM for wood dust or 4,500 FPM for metal grindings), dust settles inside ducts, creating extreme fire and explosion hazards.