Refrigerant Suction Riser & Oil Return Calculator engineering
100% Free • No Sign-Up

Refrigerant Suction Riser & Oil Return Calculator

Determine minimum entrainment vapor velocity (fpm), vertical suction riser pipe sizing, and double suction riser necessity under part-load compressor unloading.

Refrigerant & Suction Conditions

E.g., 1 of 4 cylinder unloaders = 25%
Type L ACR: 1-5/8" = 1.625, 2-1/8" = 2.125

Velocity & Oil Return Results

Velocity at Minimum Turndown:
ASHRAE Minimum Required Velocity:
Oil Entrainment Status:
Full Load Vapor Velocity:
Double Suction Riser Required:
Full Load Pressure Drop Penalty:

Recommended Tools & Equipment

Tested hardware and components for high reliability

100% Free Tool Zero Sign-Up

ASHRAE Refrigerant Suction Riser Design Rules

Compressor crankcase lubricating oil continuously circulates into the refrigeration system. In horizontal lines, gravity and fluid shear drag the oil film along; however, in vertical upward suction risers, gas velocity must exceed a critical entrainment threshold ($1,000 - 1,200 ext{ fpm}$) to drag oil droplets upward against gravity.

Double Suction Riser Arrangement

When an unloaded compressor drops to $25% - 50%$ capacity, a large single pipe experiences low vapor velocity ($< 700 ext{ fpm}$), causing oil to settle and pool at the base of the riser until the compressor seizes from crankcase oil starvation. A double suction riser with an inverted P-trap automatically seals off the larger leg at part load, forcing all vapor through the smaller leg to maintain high velocity.