Safety Valve Gas Orifice Calculator (API 520)
Size pressure safety relief valve (PSV) effective orifice areas and select standard API 526 letter designations (D through T) for gas and vapor service.
Relief Sizing Parameters
Backpressure & Coefficients
PSV Sizing & API 526 Orifice
Recommended Tools & Equipment
Tested hardware and components for high reliability
Frequently Asked Questions
What are API 526 standard orifice letter designations?
API Standard 526 standardizes relief valve nozzle sizes and body dimensions into 14 distinct orifice letters ranging from D (0.110 in²) up to T (26.0 in²). Relief valve manufacturers design their cast bodies to match these exact standard throat areas.
When does API 520 require a Balanced Bellows instead of a Conventional PSV?
Conventional valves vent the back of the disc holder to the discharge header. If superimposed or built-up backpressure exceeds 10% of set pressure, the backpressure acts on top of the disc, artificially raising the opening pressure and choking capacity. Balanced bellows isolate the disc, permitting backpressures up to 30 - 50%.
What allowable overpressures are permitted by ASME Section VIII?