AnythingOnline
3-Phase Motor FLA & Branch Circuit Calculator electrical
100% Free • No Sign-Up

3-Phase Motor FLA & Branch Circuit Calculator

Determine 3-phase AC motor full load current (FLA), 125% minimum wire sizing ampacity, and maximum overcurrent protection per NEC Article 430.

Motor Rating & Voltage

Branch Circuit Overcurrent Device

Motor Current & Sizing Results

Motor Full Load Amps (FLA)
-- Amps
-- A (NEC Table 430.250 benchmark)
Min Conductor Ampacity
-- A
125% of FLA (NEC 430.22)
Maximum Breaker / Fuse
-- A
-- A standard trip
Electrical Input Power: -- kW
Apparent Power: -- kVA
Recommended Copper Conductor: -- AWG 75°C THHN
NEC 430.6 mandates using NEC Table 430.250 values rather than motor nameplate for sizing branch circuit conductors and breakers.

Recommended Tools & Equipment

Tested hardware and components for high reliability

100% Free Tool Zero Sign-Up

Frequently Asked Questions

Why does the NEC require Table 430.250 values instead of motor nameplate FLA?

Per NEC 430.6(A)(1), conductors, switches, and branch-circuit overcurrent protection must be sized using NEC table values rather than actual motor nameplate amps. This guarantees that if a motor is replaced in the future with a lower-efficiency motor of the same horsepower, the wiring will not be undersized.

Why can a motor circuit breaker be sized up to 250% of FLA?

Standard 3-phase induction motors draw 600% to 800% of their full load current during across-the-line starting. To prevent nuisance tripping during rotor acceleration while still providing short-circuit protection, NEC 430.52 allows inverse-time breakers to be sized up to 250% of FLA (separate thermal overload relays protect against motor running overloads).

What is the 125% branch circuit conductor multiplier in NEC 430.22?

Conductors supplying a single continuous-duty motor must have an allowable ampacity of not less than 125% of the motor full-load current rating to accommodate sustained continuous heating under full load.