⚡ AnythingOnline
⚡
3-Phase Motor FLA & Branch Circuit Calculator electrical
100% Free • No Sign-Up

3-Phase Motor FLA & Branch Circuit Calculator

Determine 3-phase AC motor full load current (FLA), 125% minimum wire sizing ampacity, and maximum overcurrent protection per NEC Article 430.

Motor Rating & Voltage

Branch Circuit Overcurrent Device

Motor Current & Sizing Results

Motor Full Load Amps (FLA)
-- Amps
-- A (NEC Table 430.250 benchmark)
Min Conductor Ampacity
-- A
125% of FLA (NEC 430.22)
Maximum Breaker / Fuse
-- A
-- A standard trip
Electrical Input Power: -- kW
Apparent Power: -- kVA
Recommended Copper Conductor: -- AWG 75°C THHN
NEC 430.6 mandates using NEC Table 430.250 values rather than motor nameplate for sizing branch circuit conductors and breakers.

Frequently Asked Questions

Why does the NEC require Table 430.250 values instead of motor nameplate FLA?

Per NEC 430.6(A)(1), conductors, switches, and branch-circuit overcurrent protection must be sized using NEC table values rather than actual motor nameplate amps. This guarantees that if a motor is replaced in the future with a lower-efficiency motor of the same horsepower, the wiring will not be undersized.

Why can a motor circuit breaker be sized up to 250% of FLA?

Standard 3-phase induction motors draw 600% to 800% of their full load current during across-the-line starting. To prevent nuisance tripping during rotor acceleration while still providing short-circuit protection, NEC 430.52 allows inverse-time breakers to be sized up to 250% of FLA (separate thermal overload relays protect against motor running overloads).

What is the 125% branch circuit conductor multiplier in NEC 430.22?

Conductors supplying a single continuous-duty motor must have an allowable ampacity of not less than 125% of the motor full-load current rating to accommodate sustained continuous heating under full load.